Delta NT-30 Online UPS, Three Phases In & Out, 30 KVA
Model NT- NT-30K
Power Rating : NT-30K : 30kVA / 24kW
Input: Nominal Voltage: 380/220
Voltage Range: 305~499 Vac
Current Harmonic Distortion: < 3% (with optional power filter, full load)
Frequency: 45~65Hz
Output: 380/220,
Output Power Factor: 0.8
Voltage Harmonic Distortion: ≤ 3% (linear load)
Voltage Regulation: ± 1% (static)
Frequency: 50/60 Hz ± 0.01% (internal oscillator), ± 1% (synchronized)
Overload Capability: ≤ 110%: 60 minutes, 110 ~ 125%: 10 minutes, 126 ~ 150%: 1 minute
Interface : Standard RS232 x 1, RS485 x 2, SMART slot x 1, Output dry contact x 6
Other Features :
Parallel Redundancy Up to 8 units
Emergency Power Off Local and remote
SRAM Event Log 500 records
Input Harmonic Improvement